Columbia-Richland Fire Department
Outdoor Festival and Special Event Regulations
Purpose
The purpose of these comprehensive guidelines is to provide information regarding fire and life safety requirements for outdoor festivals and special events; and to establish the responsibilities for event promoters, sponsors and vendors to follow to those requirements within the City limits of Columbia. It is our mission to ensure Fire and Life Safety measures are taken to protect the patrons and vendors, and that it is strictly adhered to. By doing so, we will assure that all endeavors are successful.
If you have any questions or comments regarding the information contained within, or if you need assistance interpreting these requirements, please contact Assistant Chief Fire Marshal, George Adams at Fire Prevention.
Office: 803 545 3701 Fax: 803 401 8839 Email: George.Adams@columbiasc.gov
Roles and Responsibilities
Event Sponsor
The event sponsor assumes overall responsibility for the set-up and operation of the festival or special event and ensures compliance with all fire and life safety guidelines and requirements. Prior to any event, the sponsor shall provide a site plan (Map) to the CRFD showing:
- The name of all streets and areas that will be used for the festival or event
- The location of emergency apparatus access lanes (minimum of 20 feet unobstructed width)
- The location of stages, non-food booths vendors, food vendors and display areas
- Locations of emergency exits
Event Vendors
Event vendors are responsible for the safe operation of their booths, display or attraction. Vendors shall coordinate the event setup and take down with the event sponsor to ensure compliance with all fire and life safety guidelines and requirements. The event vendors shall:
- Keep fire lanes and emergency vehicle access, fire department connections and building access clear and unobstructed
- Be prepared at any time for a fire inspection
- Correct any identified violations of fire safety requirements 30 minutes prior to opening for business
- Failure to comply may result in closure of the individual booth until reasonable compliance is achieved.
- Maintain compliance with all fire and life safety guidelines and requirements throughout the duration of the festival or event
- Read, understand and adhere to the Fire Safety Requirements of Food Trucks.
https://www.nfpa.org/Codes-and-Standards/Resources/Standards-in-action/Food-truck-safety
Food Truck Video:
Fire Department Inspection
The fire department Fire Prevention Division is responsible for inspecting festivals and events in which a site inspection is deemed necessary prior to the opening of the event. The marshals will issue correction notices when non-compliant conditions needing correction are found and will re-inspect to ensure compliance. The fire department inspections shall include, but not be limited to the following:
- Food Trucks concession booths
- Fire department and emergency apparatus access
- Access to fire hydrants, fire department connections, and fire control rooms
- Event egress
- Generator placement
- Propane tank placement, security, and leaks
- Pyrotechnics and open flame effects
- Tents requiring a permit
- Tents requiring anchorage
- Fire extinguishers
- Hood suppression systems
-
On duty personnel
IFC 403.12.1: Fire watch personnel
When, in the opinion of the fire code official, it is essential for public safety in a place of assembly or any other place where people congregate, because of the number of persons, or the nature of the performance, exhibition, display, contest or activity, the owner, agent or lessee shall provide one or more fire watch personnel, as required and approved, to remain on duty during the times such places are open to the public, or when such activity is being conducted, this person shall be a Deputy Fire Marshal.
-
Public safety plan
Where the fire code official determines that an indoor or outdoor gathering of persons has an adverse impact on public safety through diminished access to buildings, structures, fire hydrants and fire apparatus access roads or where such gatherings adversely affect public safety services of any kind, the fire code official shall have the authority to order the development of, or prescribe a plan for, the provision of an approved level of public safety.
The public safety plan shall address such items as emergency vehicle ingress and egress, fire protection, emergency medical services, public assembly areas and the directing of attendees and vehicles (including the parking of vehicles), vendor and food concession distribution, and the need for the presence of law enforcement, and fire and emergency medical services personnel at the event.
404.2.1 Fire evacuation plans.
Fire evacuation plans shall include the following:
- Emergency egress or escape routes and whether evacuation of the building is to be complete or, where approved, by selected floors or areas only.
- Procedures for employees who must remain to operate critical equipment before evacuating.
- Procedures for accounting for employees and occupants after evacuation has been completed.
- Identification and assignment of personnel responsible for rescue or emergency medical aid.
- The preferred and any alternative means of notifying occupants of a fire or emergency.
- The preferred and any alternative means of reporting fires and other emergencies to the fire department or designated emergency response organization.
- Identification and assignment of personnel who can be contacted for further information or explanation of duties under the plan.
- A description of the emergency voice/alarm communication system alert tone and preprogrammed voice messages, where provided.
404.2.2 Fire safety plans.
Fire safety plans shall include the following:
- The procedure for reporting a fire or other emergency.
- The life safety strategy and procedures for notifying, relocating, or evacuating occupants.
- Site plans indicating the following:
3.1. The occupancy assembly point.
3.2. The locations of fire hydrants.
3.3. The normal routes of fire department vehicle access.
- Floor plans identifying the locations of the following:
4.1. Exits.
4.2. Primary evacuation routes.
4.3. Secondary evacuation routes.
4.4. Accessible egress routes.
4.5. Areas of refuge.
4.6. Manual fire alarm boxes.
4.7. Portable fire extinguishers.
4.8. Occupant-use hose stations.
4.9. Fire alarm annunciators and controls.
- A list of major fire hazards associated with the normal use and occupancy of the premises, including maintenance and housekeeping procedures.
- Identification and assignment of personnel responsible for maintenance of systems and equipment installed to prevent or control fires.
- Identification and assignment of personnel responsible for maintenance, housekeeping and controlling fuel hazard sources.
-
Fire Department Access
During events it is exclusively imperative to keep access for fire and emergency apparatus. This would include access for both fire engines/trucks and medical transport units. To ensure a safe event, all required emergency access shall be maintained open and unobstructed at all times.
Access to water supplies
507.5.4 Obstruction- Access to fire hydrants shall be maintained clear and unobstructed Fire hydrants shall not be obscured from visibility.
507.5.5 Clear space around hydrants- A clear space of 3 feet measured from the top/center of the hydrant shall be maintained in all directions.
503.2.1 IFC: Dimensions.
Fire lanes and fire apparatus access roads shall have an unobstructed width of not less than 20 feet (6096 mm), and an unobstructed vertical clearance of not less than 13 feet 6 inches (4115 mm).
503.4 IFC: Obstruction of fire apparatus access roads.
Fire apparatus access roads shall not be obstructed in any manner, including the parking of vehicles, equipment, vendors or public. The minimum widths and clearances shall be maintained at all times and shall be the responsibility of the owner or representative to keep the fire lanes free and unobstructed at all times.
-
Electrical
604.5 IFC: Extension cords.
Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.
Extension cords and electrical wiring shall be properly secured tot the ground to prevent trip hazards.
604.5.1 IFC: Power supply.
Extension cords (UL/FM listed) shall be plugged directly into an approved receptacle, power tap or multiplug adapter and, except for approved multiplug extension cords, shall serve only one portable appliance.
604.5.2 IFC: Ampacity.
The ampacity of the extension cords shall not be less than the rated capacity of the portable appliance supplied by the cord.
604.5.3 IFC: Maintenance.
Extension cords shall be maintained in good condition without splices, deterioration or damage.
604.5.4 Grounding.
Extension cords shall be grounded when serving grounded portable appliances
604.6 Unapproved conditions.
Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
-
TEMPORARY AND PERMANENT TENTS AND MEMBRANE STRUCTURES
3104.1 IFC: General.
All tents, membrane structures, both temporary and permanent, shall be in accordance with this section. Permanent tents and membrane structures shall also comply with the International Building Code.
3104.2 IFC: Flame propagation performance treatment.
Before a permit is granted, the owner or agent shall file with the fire code official a certificate executed by an approved testing laboratory certifying that the tents, membrane structures and their appurtenances; sidewalls, drops and tarpaulins; floor coverings, bunting and combustible decorative materials and effects, including sawdust when used on floors or passageways, shall be composed of material meeting the flame propagation performance criteria of NFPA 701 or shall be treated with a flame retardant in an approved manner and meet the flame propagation performance criteria of NFPA 701, and that such flame propagation performance criteria are effective for the period specified by the permit.
* Tents that are marked with a seal from the California State Fire Marshal or any other entity shall be prohibited.
3103.2 IFC: Approval required.
Tents and membrane structures having an area in excess of 200 square feet (19 m 2 ) and canopies in excess of 400 square feet (37 m 2 ) shall not be erected, operated or maintained for any purpose without first obtaining a permit and approval from the fire code official.
Exceptions:
- Tents used exclusively for recreational camping purposes.
- Fabric canopies open on all sides which comply with all of the following:
2.1. Individual canopies having a maximum size of 700 square feet (65 m 2).
2.2. The aggregate area of multiple canopies placed side by side without a fire break clearance of 12 feet (3658 mm), not exceeding 700 square feet (65 m 2) total.
2.3. A minimum clearance of 12 feet (3658 mm) to all structures and other tents.
Anchoring and Securing Tents and Membrane Structures:
3103.9 Anchorage required.
Tents, membrane structures and their appurtenances shall be adequately roped, braced and anchored to withstand the elements of weather and prevent against collapsing. Documentation of structural stability shall be furnished to the fire code official on request. A minimum weight of 50 pounds and shall be applied to each corner for small event tents (10 x10). Larger tents shall be secured and staked as approved by the Fire Marshal. (Note: Merchandise that’s intended for sale or distribution shall not be used as anchoring for tents such as clothing or coolers.)
(Note: In the event of inclement weather of excessive wind conditions, regardless of the weight anchorage you may instructed to take down your tent.)
3104.4 IFC: Certification.
An affidavit or affirmation shall be submitted to the fire code official and a copy retained on the premises on which the tent or air-supported structure is located. The affidavit shall attest to the following information relative to the flame propagation performance criteria of the fabric:
- Names and address of the owners of the tent, canopy or air-supported structure.
- Date the fabric was last treated with flame-retardant solution.
- Trade name or kind of chemical used in treatment.
- Name of person or firm treating the material.
- Name of testing agency and test standard by which the fabric was tested.
Fire Precautions for Tents, Temporary and Permanent and Membrane Structures:
3107.2 IFC: Combustible materials.
Hay, straw, shavings or similar combustible materials shall not be located within any tent or membrane structure containing assembly occupancy, except the materials necessary for the daily feeding and care of animals. Sawdust and shavings utilized for a public performance or exhibit shall not be prohibited provided the sawdust and shavings are kept damp. Combustible materials shall not be permitted under stands or seats at any time. The areas within and adjacent to the tent or air-supported structure shall be maintained clear of all combustible materials or vegetation that could create a fire hazard within 20 feet (6096 mm) of the structure. Combustible trash shall be removed at least once a day from the structure during the period the structure is occupied by the public.
3107.3 IFC: Smoking.
Smoking shall not be permitted in tents or membrane structures. Approved “No Smoking” signs shall be conspicuously posted.
3107.4 IFC: Open or exposed flame.
Open flame or other devices emitting flame, fire or heat or any flammable or combustible liquids, gas, charcoal or other cooking device or any other unapproved devices shall not be permitted inside or located within 20 feet (6096 mm) of the tent or membrane structures while open to the public unless approved by the fire code official. (This means charcoal or catalytic heaters)
3107.5 IFC: Fireworks.
Fireworks shall not be used within 100 feet (30 480 mm) of tents or membrane structures.
3107.6 IFC: Spot lighting.
Spot or effect lighting shall only be by electricity, and all combustible construction located within 6 feet (1829 mm) of such equipment shall be protected with approved noncombustible insulation not less than 9.25 inches (235 mm) thick.
3107.8 IFC: Clearance.
There shall be a minimum clearance of at least 3 feet (914 mm) between the fabric envelope and all contents located inside the tent or membrane structure.
3107.9 IFC: Portable fire extinguishers.
Portable fire extinguishers shall be provided, a minimum of a 2A10BC in size.
3107.10 IFC: Fire protection equipment.
Fire hose lines, water supplies and other auxiliary fire equipment shall be maintained at the site in such numbers and sizes as required by the fire code official. (Large Scale events)
Number of Persons allowed in Assembly Tent/Membrane Structure.
3107.11 IFC: Occupant load factors.
The occupant load allowed in an assembly structure, or portion thereof, shall be determined in accordance with Chapter 10 of the IFC and the Fire Marshal.
Heating and Cooking inside Tents
3107.12 IFC: Heating and cooking equipment.
Heating and cooking equipment shall be installed in accordance with the Mechanical Code, and sections listed below.
3107.12.1 Installation.
Heating or cooking equipment, tanks, piping, hoses, fittings, valves, tubing and other related components shall be installed as specified in the International Mechanical Code and the International Fuel Gas Code, and shall be approved by the fire code official.
3107.12.2 Venting.
Gas, liquid and solid fuel-burning equipment designed to be vented shall be vented to the outside air as specified in the International Fuel Gas Code and the International Mechanical Code. Such vents shall be equipped with approved spark arresters when required. Where vents or flues are used, all portions of the tent or membrane structure shall be not less than 12 inches (305 mm) from the flue or vent.
3101.12.3 Location.
Cooking and heating equipment shall not be located within 10 feet (3048 mm) of exits or combustible materials.
3104.15.4 Operations.
Operations such as warming of foods, cooking demonstrations and similar operations that use solid flammables, butane or other similar devices which do not pose an ignition hazard, shall be approved by the Fire Marshal..
3104.15.5 Cooking tents.
Tents where cooking only is performed shall be separated from other tents, canopies or membrane structures by a minimum of 20 feet (6096 mm). All tents shall meet the requirements of NFPA 701 as listed above
All cooking areas shall be segregated by at least a 4ft barrier to prevent traffic flow and accidental injuries.
3104.15.6 Outdoor cooking.
Outdoor cooking that produces sparks or grease-laden vapors shall not be performed within 20 feet (6096 mm) of a tent, canopy or membrane structure.
3104.16.2 IFC: Location of LP Gas containers.
LP-gas containers shall be located outside. Safety release valves shall be pointed away from the tent, canopy or membrane structure.
3104.16.2.1 Containers 500 gallons or less.
Portable LP-gas containers with a capacity of 500 gallons (1893 L) or less shall have a minimum separation between the container and structure not less than 10 feet (3048 mm).
3104.16.2.2 Containers more than 500 gallons.
Portable LP-gas containers with a capacity of more than 500 gallons (1893 L) shall have a minimum separation between the container and structures not less than 25 feet (7620 mm).
3104.16.3 Protection and security.
Portable LP-gas containers, piping, valves and fittings which are located outside and are being used to fuel equipment inside a tent, canopy or membrane structure shall be adequately protected to prevent tampering, damage by vehicles or other hazards and shall be located in an approved location. Portable LP-gas containers shall be securely fastened in place to prevent unauthorized movement.
3104.17.1 Use.
Flammable-liquid-fueled equipment shall not be used in tents, canopies or membrane structures.
(Because of harmful fumes and the potential of fuel spills)
3104.18 IFC: Display of motor vehicles inside tents.
Liquid- and gas-fueled vehicles and equipment used for display within tents, canopies or membrane structures shall be in accordance with the following sections;
3104.18.1 Batteries.
Batteries shall be disconnected in an appropriate manner.
3104.18.2 Fuel systems.
Vehicles or equipment shall not be fueled or defueled within the tent, canopy or membrane structure.
3104.18.2.1 Quantity limit.
Fuel in the fuel tank shall not exceed one-quarter of the tank capacity or 5 gallons (19 L), whichever is less.
3104.18.2.2 Inspection.
Fuel systems shall be inspected for leaks.
3104.18.2.3 Closure.
Fuel tank openings shall be locked and sealed to prevent the escape of vapors.
3104.18.3 Location.
The location of vehicles or equipment shall not obstruct means of egress.
3104.18.4 Places of assembly. (Convention Centers and Exhibit)
When a compressed natural gas (CNG) or liquefied petroleum gas (LP-gas) powered vehicle is parked inside a place of assembly, all the following conditions shall be met:
- The quarter-turn shutoff valve or other shutoff valve on the outlet of the CNG or LP-gas container shall be closed and the engine shall be operated until it stops. Valves shall remain closed while the vehicle is indoors.
- The hot lead of the battery shall be disconnected.
- Dual-fuel vehicles equipped to operate on gasoline and CNG or LP-gas shall comply with the above sections.
3104.18.5 Competitions and demonstrations.
Liquid- and gas-fueled vehicles and equipment used for competition or demonstration within a tent, canopy or membrane structure shall comply with the following sections;
3104.18.5.1 Fuel storage.
Fuel for vehicles or equipment shall be stored in approved containers in an approved location outside of the structure, not less than 50 feet from tents or membrane structures.
3104.18.5.2 Fueling.
Refueling shall be performed outside of the structure in an approved location by the Fire Marshal, at least 20feet away.
3104.18.5.3 Spills.
Fuel spills shall be reported and cleaned up immediately.
3104.19 Separation of generators.
All extension cords shall be approved for exterior use and shall not pose a tripping hazard.
Generators must be located so that exhaust does not enter buildings, mobile trailers or tents.
Generators and other internal combustion power sources shall be separated from tents or membrane structures and shall be placed only in locations approved for festival use. In addition, generators shall be isolated from contact with the public by fencing, enclosure or other approved means.
One 2A:20BC portable fire extinguisher shall be located near the generator.
Smoking and open flames shall be prohibited within 25 feet.
The Fire Marshal assigned must remain on site during duration of the event
Refueling of generators shall be prohibited during event hours.
3104.20 Standby personnel.
When, in the opinion of the fire code official, it is essential for public safety in a tent, canopy or membrane structure used as a place of assembly or any other use where people congregate, because of the number of persons, or the nature of the performance, exhibition, display, contest or activity, the owner, agent or lessee shall employ one or more qualified persons, as required and approved (Deputy Fire Marshal), to remain on duty during the times such places are open to the public, or when such activity is being conducted.
Before each performance or the start of such activity, standby personnel shall keep diligent watch for fires during the time such place is open to the public or such activity is being conducted and take prompt measures for extinguishment of fires that occur and assist in the evacuation of the public from the structure.
There shall be trained crowd managers or crowd manager supervisors at a ratio of one crowd manager/supervisor for every 250 occupants, as approved.
3104.21 IFC: Vegetation removal.
Combustible vegetation shall be removed from the area occupied by a tent, canopy or membrane structure, and from areas within 30 feet (9144 mm) of such structures.
3104.22 IFC: Waste material.
The floor surface inside tents, canopies or membrane structures and the grounds outside and within a 30-foot (9144 mm) perimeter shall be kept clear of combustible waste. Such waste shall be stored in approved containers until removed from the premises.
-
Fire Extinguishers
Any vendor or concession that utilizes cooking or heating devices shall have a minimum of:
One 2A10BC portable fire extinguisher AND One Class K type portable fire extinguisher if deep frying operation is in use.
The extinguishers must be “in date” with a current inspection tag, (not in need of servicing), visible, accessible and mounted (not sitting on the ground).
-
LP Gas Cylinders
All compressed gas cylinders, hoses and any other devices shall meet the requirements of NFPA 58. All cylinders shall be properly secured to prevent them from falling or knocked over.
-
Open Burning
All open burning is prohibited in the City of Columbia. Recreational burning is allowed with the express permission of the Fire Marshal.
-
Indoor Displays
314.4 Vehicles.
Liquid- or gas-fueled vehicles, boats or other motorcraft shall not be located indoors except as follows:
- Batteries are disconnected.
- Fuel in fuel tanks does not exceed one-quarter tank or 5 gallons (19 L) (whichever is least).
- Fuel tanks and fill openings are closed and sealed to prevent tampering.
- Vehicles, boats or other motorcraft equipment are not fueled or defueled within the building.
-
Fireworks
3308.1 IFC: General.
The use and display of fireworks, including proximate audience displays and pyrotechnic special effects in motion picture, television, theatrical, and group entertainment productions, shall be prohibited unless
handled by an approved, competent, South Carolina Licensed pyrotechnical operator.
Prior approval is required from the Columbia Fire Prevention Division and SC State Fire Marshals office.
Special Event Checklist:
- All permits have been applied for and approved?
- Fire evacuation plan has been submitted and approved?
- Fire Extinguishers have been checked and serviced?
- All appliances are UL listed and in good working condition?
- Prior arrangements have been made for the use of power on site?